Locate the setting (common in FTDI chips) and drop it from the default 16ms down to 1ms or 2ms . This forces the adapter to flush data to your PC immediately.

Cheap, non-isolated adapters often struggle with high baud rates. If you’re seeing missing bytes consistently, try lowering your baud rate to 9600 to see if stability improves. 2. Adjust Modbus Poll Timeout Settings modbus poll bytes missing error fixed

Baud rate, parity, or stop bit mismatches corrupt the data stream, leading to missing bytes. Match Master and Slave Settings Locate the setting (common in FTDI chips) and

What (e.g., PLC, power meter, sensor) are you trying to read? Share public link If you’re seeing missing bytes consistently, try lowering

Open Communication Traffic Display ( Display > Communication ) View raw RX/TX hex values to see exact byte counts. Increase Response Timeout to 3000ms Rules out slow processing speeds on the slave device. 3 Add 120-Ohm termination resistors Stabilizes voltage reflections on long RS485 lines. 4 Verify Parity / Stop Bit rules

Enable "Log to File" in Modbus Poll, then examine the raw hex. The exact point where bytes go missing (beginning, middle, or end) tells you if it's a timing, hardware, or protocol issue.